Details: sub head-i : addressable fire detection and alarm system [for main t.e. buildings] supplying, installation, testing & commissioning of micro processor based 2 wire fault tolerant, fire alarm/detection 1 loop addressable main fire control panel capable of supporting not less than 99 devices (including detectors) per loop. the panel shall be able to give location of all fire/fault conditions of addressable units via the address codes. further, the panel must be able to automatically switch on /off the respective control module when ever any alarm is triggered. the panel shall have rectifier, inbuilt loop cards, lcd/ touch screen or other keypad and events history log in the non volatile memory (eprom), display unit to indicate fire/fault signal with address and analog output, complete in all respects. the panel shall be steel sheet powder coated / abs plastic sealed to ip30. the panel shall have led indicators for indication of various signal [approved makes : honeywell morley/ notifie
Sector: Telecommunication