Description: C o MCH Block in Regional Hospital at Una Distt Una SH Providing Installation Testing and commissioning of automatic fire alarm and P A system therein Name of Work C O MCH Block in Regional Hospital at Una Distt Una HP SH Providing Installation Testing and Commissioning of automatic fire alarm PA system therein
Details: Supply, Installation, Testing and Commissioning of addressable multisensor smoke detector including mounting base with LED… etc. complete as required with 2 inbuilt Isolators as per NFPA 72 style 7 wiring requirements (one for incoming and one for outgoing line) for maintaining operational availability of all elements in the loop in the event of a short circuit and to meet style 7 requirements; Drift Compensation feature & Automatic addressing. Detector should monitor Electromagnetic interference and report to the panel - current and average values.Detector should have IP40 or better protection rating. EMC safety for detector shall be 50 V/m. Shall be UL/EN/VDS certification. (Detectors without Inbuilt Isolators may be considered with an additional Isolator Module per detector). Approved Makes: Nohimi, Autronica, Bosch , Sinteso , Notifire. Supply, Installation, Testing and Commissioning of addressable Heat detector including mounting base with LED… etc. complete as requiredwit
Sector: PWD