Description: REPAIR REPLACEMENT OF SWITCHGEAR CHANGEOVER SWITCH BUS BAR RELAYS LBS WITH CONNECTED ACCESSORIES AT KARU ZONE I II AND SHESHARTHANG UNDER GE 860 EWS Name of Work REPAIR REPLACEMENT OF SWITCHGEAR CHANGEOVER SWITCH BUS BAR RELAYS LBS WITH CONNECTED ACCESSORIES AT KARU ZONE I II AND SHESHARTHANG UNDER GE 860 EWS
Details: S&F in replacement of LT FPB made out of CRCA sheet 3 mm thick outdoor Pedestal type totally enclosed with front and rear opening, hinged doors with projected an raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for cables, danger notice plate, strickering of Switcher gear about termination of switch gear, and the nuts/ bolts etc used are to be made of rust proof material incl as per IS: 8623 tinned copper bus bar with insulators suitable for three phase and four wire LT AC, 50 Hz 415 V 1500 A capacity complete with powder coating, necessary internal electric connection as required and provision of the following: Incoming: LT switch gear 440 Volts 3 phase, 4 wire 50 cycles, cubicle or truck type complete with air circuit breaker, with microprocessor release IPR -E eleteical draw type 1000 Amp, 100 KA , overload protection, no-volt release with necessary CTs,meter and cable boxes of rating upto
Sector: Defense