Description: Procurement of SWAS System spares for 2x500 MW DTPS Anpara Name of Work Procurement of SWAS System spares for 2x500 MW DTPS Anpara
Details: Supply of SWAS System spares for 2x500 MW, DTPS Anpara SAMPLE COOLER --PART NO.: DHX-6-0-0-0-0 SHELL- [DESIGN= TUBE COIL IN SHELL COUNTER FLOW; MOUNTING = SURFACE; MATERIAL= ASTM A312, TP-304; DESIGN PRESSURE= 10Kg/Cm2; TEST PRESSURE= 15 Kg/Cm2 ; MAX CW PRESSURE= 6-7 Kg/Cm2; BAFFLE MATERIAL = ASTM A312.TP-304; ], COIL- [LENGTH = 6 mtr coil; MATERIAL= ASTMA214, TP316 seamless; TUBE OD X THICKNESS = 1/4"OD, 20 SWG; TEST PRESSURE= 375 Kg/Cm2; MAX SAMPLE PRESSURE= 250 Kg/Cm2 ; MAX SAMPLE TEMP.= 560 Deg.C.], COOLING WATER-[PRESSURE = 2 - 7 Kg/Cm2 ; TEMPERATURE = 35 ~46 Deg. C. ; ], CONNECTION- [SAMPLE INLET = 1/4" OD ; SAMPLE OUTLET = 1/4" OD; COOLING WATER = 3/4" NPT(F) ] SAMPLE COOLER -- PART NO.: DHX-18-0-0-0-0 SHELL- [DESIGN= TUBE COIL IN SHELL COUNTER FLOW; MOUNTING = SURFACE; MATERIAL= ASTM A312, TP-304; DESIGN PRESSURE= 10Kg/Cm2; TEST PRESSURE=
Sector: Generation