Details: supply, fixing and testing of conventional manual call point 24v resettable type, each mcp installed on the loop shall have a unique address, set at the commissioning stage by means of a seven-segment dil switch. the elapsed time between activation of the mcp and initiation of the sounders in an alarm condition via command from the fire alarm control panel shall not exceed three seconds complete in all respect as specified or indicated including testing on completion. complete all as specified and directed by the engineer-in-charge. repairing and testing of existing unserviceable and manual call point including opening, soldering of circuits, cleaning, replacement of glass, testing and painting complete all as specified and directed by engr-in-charge. supply fixing and testing loop powered sounder strobe 24v. dual tone shall be of electronic type and shall give discontinuous/ intermittent audible alaram. the line matching transformer shall be provided complete in all respect as s