Description: MAINT OF LT FEEDER PANELS AND VARIOUS LT BREAKERS INCL RERPLACEMENT OF OLD EARTHING UG CABLES OF MD AND OTM ACCN AT EME WKSP QMTI MAP AND RH AND REP AND MAINT INCL REPLACEMENT OF SPARE AND SERVICING OF FIRE HYDRANT PUMPS AND FIRE WATER MAINS AT MH Name of Work MAINT OF LT FEEDER PANELS AND VARIOUS LT BREAKERS INCL RERPLACEMENT OF OLD EARTHING AND UG CABLES OF MD AND OTM ACCN AT EME WORKSHOP QMTI MAP AND RANGE HILLS AREA AND REPAIR AND MAINT INCL REPLACEMENT OF SPARE AND SERVICING OF FIRE HYDRANT PUMPS AND FIRE WATER MAINS AT MH KHADKI UNDER GE MH RH KHADKI
Details: Supply, install testing and commissioning in replacement factory made out door type LT panel board of size not less than 1.5 mtrx1mtrx0.450 mtr, 440 volts , 3 phase , 4 wire system with powder coating provided to make it dust /vermin proo,f manufactured from CPRI approved manufacturer, The panel shall be made with 3.15 mm thick CRCA sheet for outer shell and inner shell made out of 1.6 mm thick CRCA sheet,double door with front openable with locking arrangement, provision of threaded earthing stud at bottom, inner shell be compartmentalized, front openable single door system lockable. Inner shell completely vermin proof and to accommodate incoming/outgoing MCCBs, MCBs, and TPN aluminium bus and extension links. Aluminium bus bar of capacity 400 Amps- 4Nos, including neutral duly insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size/rating of epoxy resin insulator all housed in suitable bus bar chamber. All control wires shall be as per the OEM r