Details: supply, installation, testing, and commissioning of power transformer step down, out door type scada compatible of capacity 1600 kva, ht 33 kv/11 kv, 3 phase, 50 cycles ac with on load tap changing arrangements with remote control panel operation on 33 kv sides to vary secondary voltage from (+) 10% to (-) 10% in steps of 1.25% (16 steps), % impedance should not be less than 6.50% at normal / common tap no. 7 including suitable marshalling box and hv terminals 3 nos outdoor bare bushings with socket and lv terminal connectors of copper to connect the transformer with ht xlpe power cable of size 185 sqmm x 3 core with aluminium conductor and lv side additional neutral with one no. solid porcelain type out door bushings with sockets on the transformer lid for earthing purpose complete in all respects with standard accessories and fittings conforming to is-2026, hv( primary) side delta and lv (secondary) side star connected including control panel of transformer. the salient featu