Description: XLPE Cable for Working Voltages up to and Including 1.1 KV as per IS 7098 (Part 1) -Supply Install Testing Commissioning of step down transformer indoor type voltage rating HT11 Bye Zero Point 433 KV out door type of capacity 200 KVA LEVEL 2 3 Phase 4 Wire 50 Hz:oil cooled core type floor mounted Delta bye star connected maximum losses as defined in vector group DYN 11 Double copper wound ONAN manual type off load tap changing facility on HT side to vary secondary voltage from minus 7 Point 5 Percent to plus 7 Point 5 Percent in steps of 2 Point 5 Percent continuous rating of capacity 200 KVA incl cable box on both HT And LT side The transformer shall be completed with all standard fittings and accessories guages first fill transformer oil as as per indication level etc and confirming to IS1180 and fittings and accessories of transformers shall confirm to IS 3639 to 1996 as amended and duly mounted on rollers as per load bearing capacity of transformer and the transformer shall have the following fittings Bye accessories fitted complete all as specified and directed