Details: supply and replacement of medical isolation panel of rating 10 kva for ot / icu (critical area), medical grade as per specifications mentioned below including removing old unsv panel any type complete with elct connections etc :-(a) the panels shall be isolated panel system as per iec 61439-1&2 only, having critical (isolated) and non-critical circuits. both circuits shall be monitored on the building management system. the monitoring parameters shall include on/off status, load monitoring and shall generate alarms if any critical parameters such as isolation is anomalous. the panel shall enable electrical shock protection: according the iec 60364-7-710 standard the solution is in compliance with the group 2 location through isolation transformer and associated monitoring system.(b) the system shall be according the iec standard, the switchgear is energy by 2 separate sourcing.(c) the “main incomer supply” is coming from the ups system. the “safety incomer supply” is coming directly f
Sector: Defense