Details: air handling units supply, installation, testing & commissioning of factory built floor mounted chilled water double skin typehorizontal/vertical air handling units made of 40 mm thick sandwitched panels with polyurethane foam(puf) insulation, complete with plug type fan, vfd driven electric motor, coil section, 10 micron pre filtersection and 5 micron micro filter section, drain pan, vfd etc. the cooling coil is of copper tubes (tubesthickness not less than 0.5 mm) and aluminium fins (min. 10fins per inch) of 6 rows deep. filter sectionwith 50 mm thick metal viscous/washable synthetic type air pre-filters efficiency 80% down to 10 micron,fine filter efficiency 99.9% down to 5 micron. tefc sq. cage induction motor suitable for 415 ± 10% volts,50hz, 3 phase ac supply including mounting and fixing arrangements, ie3 motor plug fan with vfddrives anti vibration springs/isolator bearings etc., drain connections, stainless steel (18g) drain pan withpuf insulation. double canvas connections o
Sector: Medical Education