Description: REPAIR AND REPLACEMENT OF LT PANELS SWITCH GEAR CONTROL CIRCUIT ASSOCIATED CABLES AND OTHER RELATED WORKS IN THE HQ A and N COMMAND AND CERTAIN OTHER AREA UNDER GE HADDO PORT BLAIR NAME OF WORK REPAIR AND REPLACEMENT OF LT PANELS SWITCH GEAR CIRCUIT ASSOCIATED CABLES AND OTHER RELATED WORKS IN THE HQ A N COMMAND AND CERTAIN OTHER AREA UNDER GE HADDO PORT BLAIR
Details: Decarbonizing / cleaning complete 35KVAR, APFC panel of 415V Volts, 3 phase, bus bar chamber with electrical connections complete, after removing the complete bus bar from the bus bar chamber, cleaning with CTC and ensure proper decarbonizing including new bakelite of adaquate size where ever required re-fixing the same after applying Becktrol (Red) solution to the spout, checking all the connections, tightening the nuts, bolts, thimbles for incoming and outgoing system complete including renewal of defective/ rusted bolts, nuts, insulators etc. complete all as specified and as directed by Engineer in charge. All as per Item No.01 herein before but of size 100KVAR. Supply & fix in repairs 5KVAR capacitor bank of box type suitable for APFC panel, Heavy duty gas filled capacitors along with necessary contactors with CTs&PTs, Indication lamps complete with suitable copper cables and CTs along with control wiring including taking down existing unserviceable Capacitor bank complete all as d
Sector: Defense