Details: cost of material (a) 110kv, 63mva power transformer 3ph 50/63mva 110/33kv copper wound outdoor power transformer with first filling of oil with 10% extra, 50hz star star(ynyn0)with rtcc,transformer cooling fans, turret mounting neutral ct with suitable ratio accuracy and common neutral load for the purpose of restricted earth fault protection & all accessories complete in all respect as per technical specifications. nifps system for 110/33kv, 63mva power transformer dga ( 6 gas) with monitoring ( scada compatible) (b) 110kv double busbar indoor gis 110kv indoor duty gis 2500a- 40ka, 3 seconds (busbar & bbm)3 phase sf6 gas insulated metal enclosed bus bars running along the length of the switchgear to interconnect each of circuit breaker bay module. each bus bar set shall be complete with 3 nos voltage transformers complete with insulated safety grounding switches, individual bay gas compartment etc.as per tender documents 110kv double bus outdoor duty gis 2500a- 40ka, 3 secondsline