Description: PROVN OF AIR CONDITIONING TO UNDERGROUND BASE OPS INCLUDING TWCC AT AF STN PANAGARH Name of Work PROVN OF AIR CONDITIONING TO UNDERGROUND BASE OPS INCLUDING TWCC AT AF STN PANAGARH
Details: Design, Supply, Installation, Testing and Commissioning of Central AC plant with the following parameters and specifications, complete all as specified and as directed. Design, Supply, Installation, Testing and Commissioning of water-cooled Scroll Chiller with multi compressors, comprising of Hermetic compressors, DX Evaporator, shell & tube condenser, suitable expansion device, suitable for operation on R-407 C refrigerant and complete in all respects as required for 50% -2 Nos working + 50% x 1 No standby of actual Cooling capacity.Water Temperature IN - 54.0 deg FWaterTemperature OUT - 44.0 deg FFouling Factor - 0.0005 FPSCondenser:WaterTemperature lN - 93 deg FWater Temperature OUT- 100.5 deg FFouling Factor - 0.001 FPSWater flow rate through Chiller - 108 USGPMWater flow rate through Condenser - 180 USGPM Supply, Installation, Testing and Commissioning of end-suction centrifugal Chilled water pump capable of delivering 108 USGPM of water against 20 mtr head comprising of the fol