Details: supply of dlp clean agent cylinder (aluminium / stainless steel seamless type) complete with 4.5kg ul listed clean agent gas (fk-5-1-12 / fm-200 / hfc-227ea / fs49c2) , high grade brass direct valves assembly, t- connectors etc. with mounting bracket, valve mounted pressure gauge and pressure switch to monitor system health and interface with facp / bms /scada for annunciation.working pressure of cylinder :15 bar and testing pressure : 25 bar and above. supply of ul listed linear pneumatic heat / fire detection tube 6/4mm (od/id) as per scope of work supply of end of line adopters as per scope of work. supply of pressure switches as per scope of work. supply of 2c x 1.5 sq. mm copper armoured cable for signalling line circuit and notification appliance circuit. supply of ul listed 10 zone master control panel with lcd display and battery backup for interfacing clean agent system pressure switch along with 02 manual call points and 02 audio-visual strobe complete with built in potent
Sector: Harbor