Details: gas suppression system supply, installation, testing and commissioning of clean gas-based fire suppression system suitable upto 2 volume. the clean agent with zero odp as per nfpa 2001, ul listed with container bs en3-8, electrical non conductive clean agent capacity 2 kgs comprising of 10m heat sensing tube (hst) made of polymide (ul/lpcb listed) size of tube 4mm id and 6mm od. the hst to be pressurized with dry nitrogen gas confirming is:1747 and connected to extinguishing agent container via a pressure release valve.the pneumatic pressure valve is a direct low pressure value with inbuilt pressure gauge integrated ball valve for pen/ close with in the valve body, with two nos outlet to connect hst. system to have audio-video monitoring panel, microprocessor based to check the health of system and pressure in the tube. system to have power pack having 12 v 7 ah 2 nos. smf battery. system to have third party integration facility as fire safety device with piezo electric buzzer 50db j