Details: / replacement of damaged 10/ 11/ 13 mtr. long steel tubular poles including excavation of pole pit as per site conditions and grouting by cement concrete 1:3:6 (1 cement: 3 coarse sand: 6 graded stone aggregate 40 mm nominal size) etc (0.38 each pole) supplying and of galvanised stay set for 1.1 kv over head lines complete with 19/ 20 mm dia x 1.8 metres long stay rod, anchor plate of size 45 cm x 45 cm x 7.5 mm thick, thimble, stay clamps, turn buckle (20 mm x 600 mm), 7/ 4.00 mm dia g.i. stay wire and 11 kv strain insulator etc in cement concrete 1:3:6 (1 cement: 3 coarse sand: 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required & stringing of conductor rabbit conductor (for all 3 nos. conductor) fabrication & of angle iron 50mm x 50mm x 6mm (4.5kg/mtr.) cross arm for 4 wire overhead line complete with clamps bolts, nuts and washers etc including drilling of holes for insulator pins etc. and painting with primer and fin
Sector: Mining