Description: Providing Fire Detection Alarm Emergency Evacuation and PA System in Block A and B Dental College Patiala Punjab Name of Work Providing Fire Detection Alarm Emergency Evacuation PA System in Block Aand B Dental College Patiala Punjab
Details: Fire Alarm,Emergency Evacuation & PA System: Supply, installation, testing & Commissioning of Microprocessor based Multi-loop, True Peer-to-Peer Networkable Addressable Fire Alarm Control Panel with minimum 600 characters LCD display, 4000 event , 1000 alarm log history events, Qwerty/ Touch Screen keypad for operation. The panel should be equipped with sufficient numbers of loops considering 20% spare capacity in each loop. Each loop shall have a capacity of minimum 250 analog addressable devices (Devices and detectors). The panel shall work in degrade mode in case of CPU failure, Products not having this feature will offer Redundant CPU. Four access levels, flash EPROM, Panel Shall include 240 volts AC power supply, automatic battery charger, 24 volts sealed lead acid batteries sufficient for 24 hours normal working and 30 mins in alarm condition. The panel shall support with Integrated 8 channel Digital Voice Evacuation System Controller capable of broadcasting Evacuation Messag
Sector: Road development