Details: supplying, installation, testing & commissioning of central govt./ state govt. authorised fire authority approved electric driven main fire pump for sprinkler / hydrant applications suitable for automatic operation and consisting of following details given as a, b, c, d, e,f,g and h. (a) horizontal single / multi stage centrifugal end suction, back pull out type pump complete for delivery of below mentioned discharge ,including bypass arrangement for testing of pump (b) material of construction : pump casing - cast iron, impellor - bronze, shaft - ss 410, packing - mechanical seal (c)pump shall be capable of furnishing not less than 150 % of rated capacity at a head not less than 65 % of the rated head. the shut off head shall not exceed 120 % of rated head (d) squirrel cage induction motor should be ie2 class as per iec 60034-2-1: 2007, iec 60034-30: 2008, & is12615:2011 suitable for 3 phase, 415 v, 50 hz, ac supply 2900 / 1450 rpm t.e.f.c confirming to ip:55 , of required hp suit
Sector: Medical and Health