Description: Procurement of 33KV Current Transformer for Out Door type Vacuum Circuit Breaker installation under CAPEX 2023 24 Name of Supply Work Procurement of 33KV Current Transformer for Out Door type Vacuum Circuit Breaker installation under CAPEX 2023 24
Details: 33KV Current Transformer for Out Door type Vacuum Circuit Breaker installation under CAPEX-2023-24. CURRENT TRANSFORMERAdditional Data:33KV, Outdoor, Single Phase, Oil Filled &Live Tank type(Hermetically sealed with Nitrogen Gas.)3 Core. Core Details asfollows.Core 1: 600-300/5A, Accuracy Class0.2,30VA.Core 2: 600-300/5A, 5P10,30VA.Core 3: 1200/5A, PS Class. (KPV>=400V, Ie<= 75mA atVk/2, RCT<= 10 Ohm. Insulation Level 70/170KVPIS: 2705(Latest Version).Ratio Selection: On Secondary Side. Rated Continuous ThermalCurrent: 120%of rated primary.M04-C13-00227, HSN: 8504 CT Junction BoxAdditional Data:CT Junction Box suitable for 4 CoreCT.Junction Box made Stainless Steel fittedwith disconnecting type TerminalBlock,Gland Plate etc.M05-E02-00003, HSN: 85389000 TERMINAL CONNECTORAdditional Data:For 33KV CT,Suitable for PantherConductor.Al.Complete with Nut bolt,bimetallic etc.Rigid Type.CT Stud 30mm.M04-C04-00679, HSN: 8479
Sector: Generation