Details: ht panel(11-kv vcb panel board, make: crompton greaves)supply & fixing of female contact trolly side, material: copper supply & fixing of lever set with spring & other accessories required. supply & fixing of tripping coil, (as per sample) supply & fixing of closing coil, (as per sample) supply & fixing of tnc switch, (as per sample) supply of ratchet wheel assembly (as per sample) supply & fixing volt meter (analog type, 0-15 kv) supply & fixing of ampere meter (analog type,0-400a) sitc of 11-kv h.t. potential transformer (p.t) of following specifications:- 3 phase dry type pt 11-kv/110v accuracy class 0.5, burden 100 va per phase system voltage 11-kv, insulation level 12/28/75 kv, voltage factor-1.2 continuous and 1.5 for 30 sec conforming to relevant is along with other accessories required for crompton greaves make ht panels.make:- savio, hans. kappa electro control. repairing, servicing & testing of (battery tripping unit) btu installed at ess bombay life building, providing repai