Details: dx system air handling unit od161947/2023_2024 : ahus: supply, store, installation, testing & commissioning of floor mounted double skin air handling units with thermal break profile with a minimum panel thickness of 50 mm or more with roof canopy, ahri / eurovent certified unit complete with dx cooling coil, didw centrifugal fan with ie3 motor with minimum w/cfm, vfd with enclosure box ( ip 21 rated for indoor and ip 55 rated for out door applications),the vfds must have active harmonic filters to limit the harmonic distortion as per ieee standards, cleanable fabric filters of merv 8 and fine filters of merv 14, heaters of following capacity condensate drain pan, coil piping connections, condensate drain connections, mixing box with dampers inbuilt flexible duct connectors in supply, return and fresh air section . the fan should deliver the design cfm at 50 hz or lower. the electrical power wiring from the isolator to
Sector: Buildings