Details: name of work: ht/lt electrification works and augmentation of power system /modernisation of millh t installation [11kv incoming and out going panels- 3panel vcb & bus pt]: design, fabrication, supply, installation, testing and commissioning of 11kv vcb panel as per the scope of work, technical specification and drawing. the panel comprises of following major components. 11 kv, 800 a, 350mva (3 sec) vcb - 3nos. [1-i/c from grid supply and 2 o/gs to 2nos 800kva octc onan existing transformers] numerial protection relays having modbus connectivity digital power analyser/meter having rs 485 communication facilities analog meters, control mcb, indication lamps, annuunciator, etc. panel lighting (led lamp) and panel heater with temperature control thermostat. current density of aluminium busbar: 0.8 amps/sq.mm. the control supply voltage is 30v dc. [refer technical specification and slds]30v dc battery, battery charger and dc db.: supply,installation, testing & commissioning of indoor
Sector: Handicraft