Details: lightning protection for home projects at sai gram od63086-2024-2025supply providing and fixing fully solid vertical air terminals for wind stability as for 1,2,3,4per is/tec-62305 part-3 meter air terminal 16mm rod tapered to 10 mm aluminium rod meter rod:for 6, 8 meter 40mm rod tapered to 16mm and then to 10min meets the requirement (is/iec 62305)semi-hard (e-almgsio5) suitable for high wind load.all air terminal must have interception tip at the top of air terminal. air terminal joining clip stainless steel ss 304 clamp required to connect horizontalair termination to vertical air termination, lightning tested for 100 ka-10/350 micro sec waveform. this is required if using 17 kg stone supports stainless steel wall clamp or 17 kg stone of 365 mm diameter, high level of stability is required to mount 1.2.3.4 meters. no of concrete stones/wall clamps depending on wind load needs to be considered. for 6& 8 meter air terminalfor mounting: tripod stand or 3 nos & 4 nos respectivel