Details: sitc of ups od88050/2024-2025:supply installation and testing and commissioning of double conversion online 1kva ups 1ph to 1ph b) input pf : 0.99 @ full load output pf : 1,input voltage range: 140v -180v with cut off output voltage 230v.thdi : ≤ 5% isolation transformer at input side. overall efficiency: 90% ,ambient temperature: 0-40°c,generator compatibility.pure sine wave battery over charge & under charge cut off.warranty 3years for ups & 4years for tubular battery.bypass arrangement.indications: digital indications of input v & a, output v & a, battery charge, temperature en/iec 620401 for general safety compatibility en/iec 620402 for electromagnetic compatibility. en/iec 620403 for performance led + lcd display service center available in each district from oem ups approved make legrand/numeric/zenrise/ abb battery c10 rated and any make of exide / quanta/panasonic.120 min backup with tubular battery with minimum vah of 3600(12v100ahx3nos) 2.3.2:supplying