Details: transformer oil replacement and filtration in fact uc, 2024-25 removal of deteriorated oil and replenishment with new oil after filteration in transfomers of capacity ranging from 750 kva to 6300 kva cited at various locations of fact-uc. scope of work includes the following activities:1. draining the existing oil from transformer tank in to separate tanks.2. opening the inspection window/ / explosion vent of the transformer through which oil flushing is carried out.3. flushing the core-coil with oil to wash out the carbon / sludge etc. 4. draining out the remaining oil from the transformer tank. 5. filling the transformer with new oil through an oil filtering machine. (the scope of oil filtration work is addressed in a separate schedule, schedule 3).6. replacing the gaskets of the inspection window, , or explosion vent that were removed for oil replacement with new and approved types. removal of deteriorated oil and replenishment with new oil after filteration in transfomers of capa