Details: sitc of air cooled chillers sitc of air cooled liquid chilling units at rated capacity complete with multiple compressor technology with dual refrigerant circuit, air-cooled condenser and chiller.chiller shall comprise of twin compressor ( type) powered by an semi-hermetic electric motor with r-134a refrigerant and drive motor suitable for 415v +/-15%, 3 phase, 50 hz etc. the chillers shall be with wye-delta closed transistion starter, microprocessor based electrical control panel with incoming disconnect isolator along with door interlock handle., starter panel must be weather-proof ip55 rated enclosure, bacnet over mstp compatible system controller with touch pad display, full charge of refrigerant, refrigerant oil, acoustic enclosure for compressors, security grilles to protect compressor, air cooled condenser with protective guard, special corrosion resistance coating as per the technical specifications and cooler, the cooler shall be with flanged end connection for cooler pi