Description: ARM of substation and feeder pillars at 51st bn itbp patiala Punjab for the year 2025 26 Name of Work Annual Repair and Maintenance of Sub Station and Feeder Pillars at 51st Bn ITBP Patiala Punjab for the year 2025 26
Details: Testing of earth resistance and Testing of earth pit including checking resistance etc and repair/ replace if required. Dehydration and Filtration of Transformer oil of 11 KV Transformer, Remove the Moisture, sludge, Acidity and mainly to improve the BDV and Resistivity of transformers oil. After Dehydration and filtration of oil the BDV (Breakdown Voltage Test) of oil should be 60 KV and above . Top up of Transformer oil in transformer 1 & 2 complete as per direction of Engineer-in charge. Servicing and Maintenance of LT ACB (Air Circuit Breakers) including cleaning of breaker with CRC-226,removal of old grease and re-greasing the same with recommended grease., Check condition of arcing contact and gap between fixed and moving arcing contacts shall be checked. Checking presence of all circlips, checking condition of ACB wiring and replace if required.etc complete as per direction of Engineer-in charge. Servicing and Maintenance of LT VCB (Vacuum Circuit Breakers) including