Details: medical service work medical gas pipe line system:supply, installation, testing and commissioning of medical gas area alarm should be digital and capable of monitoring : 1 gas (oxygen): - medical gas area alarm panel shall be capable of monitoring medical gas services by means of pressure sensors, which detect deviations from the normal operating limits of either pressure or medical vacuum. the cover and backbox shall be polyester powder coated. a single tamperproof fastener shall be used to gain access to the hinged door. each gas service shall be displayed by colored 7” lcd touch screen to display the pipeline pressure and status for normal and fault conditions. an audible warning shall sound simultaneously with any failure indication and a mute facility shall be provided. following a mute selection the audible will resound after approximately 15 minutes, or shall operate simultaneously should a further alarm condition occur. a “mute” switch shall be provided inside the panel for u