Details: design, supply, lifting & shifting at actual proposed location of site, installation, testing & commissioning of floor mounted air handling units as specified below; double skinned powder coated inner & outer skin of 0.6 mm & 43 mm thick, 40 kg / m3 puf sandwitched insulated aluminium sectionalized construction comprising of fan section with 50 mm static best efficiency plug type fan driven by suitable pole eff - 1 tefc motor with drive package driven by ip55 / 4p tefc fan motor / fire resistant flexible fan outlet connection, the ahu shall comprise filter section with air filtering media with 10 micron pre filter, cooling coil section with chilled water coil complete with copper tube 13 fpi al finned 4r deep chilled water cooling coils, ss 304 condensate drain pan duly insulated with 15 mm thick cross linked polymer nitrile rubber insulation, with mixing box with aluminium aerofoil damper for supply, return & fresh air, necessary vibration isolation. 7750 cfm. complete in all respect