Details: supplying, installing, testing and commissioning with perfect aligning, proper levelling of fire service main single stage pump, of 2400 lpm at 76 m head centrifugal type, 75 hp (55 kw) 3 phase, 415 volt, 50hz or of suitable hp complete as per specification no. ff-mfp/ssc supplying, installing, testing and commissioning with perfect aligning, proper levelling of jockey pump of 240 lpm at 56 m head, 15 hp (11 kw), 3 phase, 415 volt, 50hz or of suitable hp with suitable stages as per specification no. ff-mfp/jp supplying, installing, testing and commissioning with perfect aligning, proper levelling of diesel engine operated fire pump, of 2280 lpm (litres/min.) at 76 m head, 30 bhp or suitable bhp with cast iron casing, bronze impellers, en-8 shaft with bronze shaft sleeves directily coupled to engine complete with ms channel base plate with coupling guard. with suitable battery, battery starting kit, battery charger, fuel tank, insulated exhaust chimney and all accessories complete as re