Details: programming and testing of new promag 10 flow transmitter. supply and installation of powder coated pannelsize: 600mm x 600mm x 400mm with electrical accessories 6amp mcb stabilizer, dual output channel spms 12vdc/24vvdc 5amp, input supply 230v ac. supply, installation, testing and commissioning of iot transponder/protocol converted with gsm/gprs connectivity for acquisition, encryption and transmission of the sensor data 2 channel , along with simcard and data pack, activated for 1 year. the device shall transmit data on lora or gsm depending on the site condition. local display shall be provided for viewing of the flow meter data, with frequency band : 850/900/1800/1900 mhz, supply voltage : 12v. transponder shall support secured transmission of telemetry via mqtt over tls with two way certificate based encryption. includes power supply to transponder and associated cabling and connections required for the data acquisition and transmission of the existing working sensor.
Sector: PWD