Details: new ht line aaac 7/3.15 mm (55mm²) (eq. to rabbit), (included 3 conductor lengths for 3-phase and additional 1 %(sag,jumpering and wastage) steel tubular pole (9 mtr.) muffs (2000 mm) with concerete filling run thro' structures (∆ formation): on single pole structures (adopt eight (8) no. run -through structures per km)- cross arm: [channel iron (100x50x6 mm), length (1270) mm i/c tolerance of 100mm either side angel iron (50x50x6 mm), length (2x750) mm pole top bracket(msci:100x50x6mm-100mm) 11 kv pin insulators (porcelain, 12 kv, 10 kn): 3 no per pole structure dead end structures: (adopt three (3) no. per km) on double pole (prefer along road side) belt set- ms angle iron : 50x50x6, length 1800mm x 2 no. x-bracing set - ms angle iron: 50x50x6, length [2125 mmx 2 no.] x-arm (horizontal)- (ms channel iron: 100x50x6, length 2340mm x 2 no.) ∆ formation discs insulator sets on dead end structures (comprising 1 no. disc: (porcelain, bs, 12 kv, 90 kn) including dead end clamps etc.) x
Sector: Distribution