Details: disconnecting 250 kva station transformer and accessories from existing arrangement of jumpers, earthings, lt cable and its plinth, safe loading onto the truck, securing it with all leads and ropes for safe and sound transportation to the works facility complete in all respect including all labour and t&p. opening of hv side bushing and removing the top plate of transformer as well as the lv side terminal and then lifting the winding from the tank with the help of crane complete in all respect including coats of all material, consumables, labour and t&p. replacement of followings damaged/non working parts/accessories, wherever required complete in all respect including cost of all material, consumables, labour and t&p. 33 kv class insulation o rings & gasket kit keyed blocks & spacers tapping leads 33 kv bushings repairing and rewinding of 1-phase hv side winding of transformer complete in all respect including coats of all material, consumables, labour and t&p. ovenning of core coi