Details: supply, retrofitting, testing & commissioning of one (01) no. of 11.5 kv, 3500 amps and three (03) nos. of 11.5 kv, 5000 amps circuit breakers. cat. no. 7330002680011.5 kv, 3 pole draw out type, acb / vcb / sf6 circuit breaker, mounted on carriage with wheels, suitable for retrofitting at existing system. confirm to iec:manually and electrically operated, racking interlock.nominal voltage: 11.5 kv, nominal current: 3500 amp.rated breaking capacity: 1000 mva, 58 ka for 3 sec.operating time: 120 ms, closing time: 400 msrated voltage of auxiliary and control circuit: 220 v dc as per bom. cat. no.73300026900 11.5 kv, 3 pole, draw out type, acb / vcb / sf6 circuit breaker, mounted on carriage with wheels, suitable for retrofitting at existing system. confirm to iec:manually and electrically operated, racking interlock.breaking capacity : 31.5 ka,making capacity : 82.5 ka,s.c. duration : 1 second,frequency