Details: servicing/periodical maintenance of d.g set of 180 kva capacity installed at filling station narwal by way of draining of engine oil, replacement of lubricating oil filter kit, fuel filter kit and air filter kit (primary & safety/secondary) and filling engine sump with lubricating oil 29 liters of 15w40 and ensuring recommended oil level with the help of dip stick/gauge. the job also involves providing and fitting of new gasket, engine hoses, sealing rings, flex fuel pipes, fan belt, inner/ outer element, flex wire flow pipes set, element lubricant oil cleaner, bracket rocker arms. servicing of radiator by way of draining of all the coolant mixture, cleaning of coolant tank, flushing radiator using flush solution, cleaning of fins and tubes with low pressure hot water and caustic soda or detergent and also by way of blowing compressed air, refilling of drained coolant mixture after its filtration and topping of coolant up to the required level. checking of all electric harnesses for
Sector: Water supply and Sewerage