Description: Replacement of old deteriorated 11kV VCB panels and installation of AC DC Board at 3x10 MVA Receiving station Awantipora I under Power Transformers and Panels 11kV VCB UT Capex 2023 24 Name of Work Replacement of old deteriorated 11kV VCB panels and installation of AC DC Board at 3x10 MVA Receiving station Awantipora I under Power Transformers and Panels 11kV VCB UT Capex 2023 24
Details: SITC of 11 kV VCB Panel Board (12 kV, 1250A, 25 kA, indoor) with O/C, E/F relays (IEC61850), Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port (1+4) (SCADA COMPATIBLE) SITC of Distribution Panel (36 V, DC) made of CRCA thickness not less than 2mm. Powder Coated, degree of protection IP43 for 2 No battery incoming supply with 2 No 63 Amps DP MCBs for incoming supply Double busbar of adequate size, 12 No DP DC MCB (0-32A) including indication lamps and cables and other accessories SITC of Distribution Panel (415 V, AC) made of CRCA thickness not less than 2mm. Powder Coated, degree of protection IP43. 200 Amps Switch Fuse disconnector for incoming supply and 5 No TPN MCB's (16-125 Amps ) and 5 No DP MCBs (0-32A), rectangular busbar suitable for 200 Amps continuous Supply including indication lamps and cables and other accessories SITC of 2 Core 2.5 mm² Control cable co
Sector: Power Sector