Details: replacement / repair of damaged components along with allied works to 600 kva manually operated voltage stabilizer installed at pump room-ii central pumping station of company bagh section. the job involves disconnecting the voltage stabilizer from three phase electric connections and dismounting the panel board. dismantling of voltage stabilizer by lifting the top assembly with the help of chain pulley block or manual labour, extracting out of core assembly. complete rewinding of coil – 01 nos. and repair to 02 no, coil. the job includes providing and fitting of two nos. rotary switches in place of damaged one. this job also involves providing and fitting of voltmeter-02 nos. ampere meter -01 n0, ct- 6 no and hrc fuse-03 nos. in place of damaged ones. replacement of bakelite stands to the terminal plate. providing and fitting of new thimbles after cutting edges of cable ends and proper dressing. the job further involves replacement of damaged wiring. topping with fresh t-oil- 300liter
Sector: Water supply and Sewerage