Description: Inatallation of lightning Protection system at Tawa Dam Tawanagar Name of Work Inatallation of lightning Protection system at Tawa Dam Tawanagar
Details: Supplying, installing, testing and commissioning of Lightning protection system with Early Streamer Emission (ESE), OPR (Optimized Pulse Rod) technology, of protection level -1, having a coverage range and mounted at a height as mentioned below including stainless steel mast & mounting structure kit as per specifications. OPR 60, radius 97Mt., Height 3 Mt Supplying, installing, testing and commissioning of Lightning Discharging Counter to verify the lighting discharge occurrence. Earthing with copper earth plate 600mmX 600mm X 3mm thick including accessories and providing masonry encloser in cement mortar, cover plate having locking arrangement on the top and G.I. watering pipe 20mm dia 2.7 metre long etc. (but without charcoal or coke and salt) complete as required Add extra for using salt and charcoal/coke for G.I. plate or copper plate earth electrode as required including excavation in hard rock and refilling the pit with black soil. Providing and fixing 25mm X 5mm copper in 4
Sector: Water Resource Department