Description: Providing and installation of central heating system hot water in existing central air condition system in C2B ward and C2A ward at AIIMS Patna Name of Work Providing and installation of central heating system hot water in existing central air condition system in C2B ward and C2A ward at AIIMS Patna
Details: Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled / Hot water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class ‘O’ insulation applied by suitable rubber based adhesive complete including repairing of damage to building etc. as per specifications and as required complete in all respect. Note:-The Pipes of sizes 150mm & below shall be M.S. ‘C’ class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above Chilled water pi
Sector: Medical Education