Details: checking trans and receive level of pilot at lmu in switch yard of 220kv s/s kirawali, agra & at 765kv s/s pgcil, agra end. checking trans and receive level of pilot at hf point of amp unit in control room of 220kv s/s kirawali, agra & at 765kv s/s pgcil, agra end.. checking the configuration of plcc t390 for channel-1 & channel 2 by connecting through proper dip 4.0 software. plcc is programmed for 20w tx power. output power of plcc is +19.5 dbm and received level as + 1.9 dbm in channel 1 and in channel 2 -tx power ; 18.7dbm and received level -0.5 dbm at 220kv s/s kirawali, agra end. at 765kv s/s pgcil, agra end output power of plcc is +18.6 dbm and received level as + 2.0 dbm in channel 1 and in channel 2 -tx power ; 18.1dbm and received level 1.5 dbm checking the protection coupler configuration at kirawali and pgcil end. adjust the guard level to 0 as it was -2.0 dbm at 220kv s/s kirawali & guard level to 0 as it was -2.8 dbm at 765kv s/s pgcil agra .transfer the tx command an