Details: supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics / lcd display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (eprom),power supply unit (230 ± 5% v, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. the panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under sh: pa system) and shall be complete with all accessories. the panel shall be compatible for ibms system with open protocol bacnet/ modbus over ip complete as per specifications. (two l