Details: dismantling and decoupling of the existing 15kw motor from existing pump set by disconnecting all the electrical and pipe lines as per direction of eic. supply and delivery at site of horizontal foot mounted squirell cage induction motor of suitable rating for driving the pump mentioned above. power supply: 415v+ 10%, 50hz + 5%, 3ph, duty-s1, tefc, ip55, class-‘f’ temp rise limited to class ‘b’, connection:sds, efficiency class-ie3 motor power should be 15% - 20% over than pump input power at duty point i.e. motor should be 18.5 kw approximately.) ambient temp. 50°c speed: 1500 rpm as sync (make:- kirloskar/cg/abb/marathon/siemens) (materials should be supplied after taking approval from department.) (all routine test to be performed in presence of eic before delivery.) supply delivery of following items: 100mm dia rising spindle sluice valves with pn 1.0 suction side side as per is 14846 spindle of is 6603, gr12 cr13 (make: ivi/ivc/kirloskar/jupitar) 100mm dia m.s pipe of 5mm thick bu
Sector: Water supply and Sewerage