Description: Supply delivery and installation of 10 KVA servo motor operated Copper wound line voltage stabilizer at PH 2 of Rajnagar Water Supply Scheme under Namkhana Block under SMD PHE Dte Name of Work Supply delivery and installation of 10 KVA servo motor operated Copper wound line voltage stabilizer at PH 2 of Rajnagar Water Supply Scheme under Namkhana Block under SMD PHE Dte
Details: N.B:-All Quoted Rates are inclusive of GST @ 18% + CESS @ 1% Charges for dismentaling the foundation of existing damaged voltage stabiliser after disconnection of power supply as per direction of EIC Supply and delivery at site of 10 KVA 3 phase, Oil cooled type servo motor operated copper wound line voltage corrector conforming to IS-9815 (Pt-)- 1994 suitable for unbalanced input voltage with following specification including first filling of oil as per IS-335 where applicable. [Make: Approved make of P.H.E. Dte.] a) Input voltage:- 3 phase main supply may or may not be balanced with respect phase to phase 200V-500V phase to neutral 115V-289V b) Output voltage: 3 phase balanced output voltage. Phase to Phase 400V 0r 415V ± 1% Phase to Neutral 230V or 240V ± 1% [provision should be made to adjust the variation of output voltage per phase by a variable well within ± 5% of output] c) Line Regulation: Output voltage should remain well within ± 1% of set voltage [from min to max i.e. e
Sector: Water supply and Sewerage