Details: detailed description of work:maintenance of 3 phase power distribution panels• checking, cleaning and servicing of all tpn switch fuse units & bus bar by tighteningall contact points after applying petroleum jelly from 32 to 630amps.switch fuseunit.• replacements of heavy duty copper lugs after cutting & dressing the conductor withglass tape & pvc tape with proper crimping of the lugs for cables ranging from 10 sq.mm. to 400 sq.mm 3½ core cable• replacement of switch fuse units with top & bottom cable entry box by fixing onexisting angle frame in case of switch fuse unit in sheet steel enclosure or by fixinginside the panel of modular type from 32 to 630amps switch-fuse unit.• replacement of voltmeters, ammeters including ct & connections complete.• painting of the whole panel by two coats enamel paint of steel grey colour & writethe room nos. /zones of distribution areas.maintenance of 3-phase power distribution boards• replacement of mcb after re- socketing & connections complete.• r