Details: supply and installation, testing and commissioning of single skinned ceiling mounted fan coil units complete with 20 gauge pre-coated sheet casing, 3 row deep chilled water coil 3/8” dia copper tubes of minimum 0.30 mm thickness, casing of g.i sheet of chilled water cooling coils having aluminum fins (12 fpi) and provision of double skin insulated sandwich type drain pan of inner 22 gauge ss and outer 22 gauge pre coated gi sheet, 12 mm thick pre filter, drain connections, tray insulation with minimum 12 mm expanded polystyrene (eps) /puff insulation with centrifugal forward curved blower, squirrel cage induction motor suitable for operation on 230 volts, single phase 50 hz ac supply as required at site. providing and fixing of 5/8”(15 mm) & 3/4” (20 mm) od supply ball valve set with strainer for each fcus complete as required. supply and making copper connections from chilled water pipe line to fcus consisting of copper tube of 5/8” (15 mm) od with straight connections, elbow f
Sector: Tourism