Details: servicing and checking of 800 amp, 11 kv schneider make vcb with blower, cleaning of existing ht panel inside, outside with tighting of all bus bar, nut & bolt, alignment, adjustment of gaps between phase to phase, checking and tightening of control wiring circuit as charging motor closing coil and tripping coil circuit, manually tripping testing of vcb, cleaning, removal of dust and dirt to male/female contacts, greasing & lubrication all moving fixed part including replacement of minor parts such as spring, washers etc. for smooth mechanical operation etc, complete with testing commissioning as required. servicing, calibration, testing of 2 element idmt relay (one earth fault one over current) with secondary injection testing of 11 kv /vcb, operational testing through relay front pad as well as push button, testing/ calibration of safety relays through secondary injection kit, tripping testing of vcb through over current and earth fault relay, tripping testing through primary injecti