Description: Supplying and replacement of old burnt out main power supply to building HT Panel in Sub Station No 4 and 2 at GTB Hospital Complex Shahdara Delhi Name of Work Supplying replacement of old burnt out main power supply to building HT Panel in Sub Station No 4 2 at GTB Hospital Complex Shahdara Delhi
Details: MAIN HT PANEL FOR SUB STATION NO. 2 Supplying, installation, testing & commissioning of indoor type floor mounted metal clad, 11 KV VCB panel with 5 Nos. VCBs, totally enclosed & fully interlocked, horizontal drawout, horizontal/ vertical isolation type breaker as per IS13118, as amended up to date and additional specifications, having capacities as mentioned below, single break, trip free mechanism, electrically charged and auto/manually closing breaker suitable for use on 11 KV, 3 Phase, 50 Hz A.C. supply with short circuit fault level of 350 MVA, complete with self contained, fully interlocked, rack in and rack out mechanism, air insulated duly PVC sleeved copper bus bars of 630 Amps capacity, breaker featured with mechanical ON/OFF indicator with hand trip device, spring release coil, shunt trip coil and auxiliary switch of 4 NO+4NC and equipped with following switchgears and accessories i/c connections suitable for 3x 300 sq. mm. XLPE 11 KV cable with bottom entry etc. complete as
Sector: PWD