Description: Supplying Installation Testing and Commissioning of 11 KV VCB Panel at sub station of Composite Hospital BSF Kadamtala Name of Work Supplying Installation Testing and Commissioning of 11 KV VCB Panel at sub station of Composite Hospital BSF Kadamtala
Details: Supplying, installation, testing and commissioning of indoor type floor mounted metal clad, 11 KV VCB panel with 04 No VCBs (01 No. incomer and 3 Nos. outgoing with VCB), totally enclosed & fully interlocked, horizontal drawout, horizontal/vertical isolation type breaker as per IS 13118, as amended up to date and additional specifications, having capacities as mentioned below, single break, trip free mechanism, manually charged and auto/manually closing breaker suitable for use on 11 KV, 3 Phase, 50 Hz AC supply with short circuit fault level of 350 MVA, complete with self-contained, fully interlocked, rack in and rack out mechanism, air insulated but encapsulated copper bus bars of 800 amps capacity, breaker featured with mechanical ON/OFF indicator with hand trip device, spring release coil, shunt trip coil and auxiliary switch of 6 NO + 6 NC and equipped with following switchgears and accessories i/c connections suitable for 3 X 240 sqmm/XLPE 11 KV cable (cable entry from bottom./
Sector: Police and Internal Security