Details: supplying, installation, testing & commissioning of indoor type floor mounted metal clad, 11 kv vcb panel with 03 no. vcbs, totally enclosed & fully interlocked, horizontal drawout, horizontal/ vertical isolation type breaker as per is 13118, as amended up to date and additional specifications, having capacities as mentioned below, single break, trip free mechanism, manually charged and auto/manually closing breaker suitable for use on 11 kv, 3 phase, 50 hz a.c. supply with short circuit fault level of 350 mva, complete with self contained, fully interlocked, rack in and rack out mechanism, air insulated but encapsulated copper bus bars of amps capacity, breaker featured with mechanical on/off indicator with hand trip device, spring release coil, shunt trip coil and auxiliary switch of 4 no+4nc and equipped with following switchgears and accessories i/c connections suitable for 3x 300 sq. mm. xlpe 11 kv cable (cable entry from *bottom/ top/side) end termination with heat shrinkable joi
Sector: University