Description: Supply AND Installation of 250kva Diesel Generator for Operation Command Centre AND ASCDCL HQ Building--Name of Work:Supply & Installation of 250kva Diesel Generator for Operation Command Centre & ASCDCL HQ Building
Details: Providing and erecting 4 Pole MCCB 415V, 250A, rated short-circuit breaking capacity 36 kA (Ics=100% of Icu) adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact and MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB(5-5-3) Supplying and erecting extended rotary handle for MCCB with adjustable telescopic rod suitable for up to 250A MCCB.(5-11-14) Supplying and erecting metal work in CRCA sheet including Iron work for supports with fabrication of boxes, panel boards, etc. including cutting, bending, drilling, welding, riveting, treated with anti-rust treatment and duly powder coated or painted with one coat of red lead paint and 2 coats of enamel paint complete.(6-1-1) Supplying and erecting iron work, sheet metal work consisting of CRCA sheets, various sections of
Sector: Smart City